S&T Project 1862 Final Report: Dielectric Frequency Response of Generator Stator Windings

Dielectric Frequency Response (DFR) testing has become an accepted test for analyzing oil filled power transformer insulation which has sparked interest in the rotating machine community. DFR testing provides similar test points compared to traditional test methods but performed at much lower test voltages. This study’s primary goal was to determine if DFR testing could provide equivalent test results to traditional test methods. Results from the study are inconsistent with respect to aligning with traditional rotating machine test methods. At times the results would correlate well, and others would differ greatly. Additional data points and study would be required to determine if these inconsistencies continue, the data correlates, or differs from traditional methods.
Download File Opens in new window
Generation Effort S&T Project 1862: Dielectric Frequency Response of Generator Stator Windings
Type Uploaded file(s)
File Type PDF
Publisher Bureau of Reclamation
Publication Date Friday, September 25th, 2020
Update Frequency not planned
Last Update Monday, June 7th, 2021

Disclaimer

The findings and conclusions of this work are those of the author(s) and do not necessarily represent the views of the Bureau of Reclamation.